TECHNICAL SPECIFICATIONS
● Dehumidification capacity (*):37.68 kg/Hr
● Air filter: G4
● Power source: 3ph/380V/50Hz
● Total power consumption: 62.725 kW
● Noise level (**): 72 dBA
DRY AIR
● Rated airflow: 5,100 m3/hr
● External static pressure : 300 Pa
● Fan motor power: 4.0 kW
REACTIVATION AIR
● Rated airflow: 1,700 m3/hr
● External static pressure : 200 Pa
● Fan motor power: 1.1 kW
GEAR MOTOR
● Motor power : 25.0 W
REACTIVATION HEATER
● Electric heater power: 57.6 kW
● Temperature increase across heater: 100 oC
● High temperature cut-out: 160oC ± 10oC
DIMENSIONS
● Width: 1450 mm
● Depth: 1500 mm
● Height: 2050 mm
● Weight: 975 kg
(*)- Conditions at 20oC/60%
(**)- Sound pressure level calculated in free field, 10 m from unit, direction factor Q = 2